+91-84089 03000

      Standard Sales Corporation

Power Contactors-ETVS (3 Pole AC Control)

Frame [Ie] Rated Operational Current   AC-1 AC-3 Motor Power at 415V, 3Ph, 50Hz   HP kW Auxiliary Contacts   NO NC Reference
FRAME 1 20 6 3 2.2 - 1 LC1E0601*
        1 - LC1E0610*
25 9 5.5 4 - 1 LC1E0901*
        1 - LC1E0910*
25 12 7.2 5.5 - 1 LC1E1201*
        1 - LC1E1210*
32 18 12 9 - 1 LC1E1801*
        1 - LC1E1810*
36 25 15 11 - 1 LC1E2501*
        1 - LC1E2510*
FRAME 2 50 32 20 15 - 1 LC1E3201*
        1 - LC1E3210*
50 38 25 18.5 - 1 LC1E3801*
        1 - LC1E3810*
50 40 29 22 - 1 LC1E40B01**
        1 - LC1E40B10**
FRAME 3 60 40 29 22 1 1 LC1E40*
70 50 34 25/30 1 1 LC1E50*
80 65 50 37 1 1 LC1E65*

Frame [Ie] Rated Operational Current AC-1 AC-3 Motor Power at 415V, 3Ph, 50Hz HP kW Auxiliary Contacts NO NC Reference
FRAME  4 110 80 60 45 1 1 LC1E80*
120 95 60 45 1 1 LC1E95*
FRAME  5 150 120 75 55 1 1 LC1E120*
200 160 120 90 1 1 LC1E160*
FRAME  6 250 200 150 110 - - LC1E200*
300 250 175 132 - - LC1E250*
FRAME  7 320 300 215 160 - - LC1E300*
500 400 295 220 - - LC1E400*
FRAME 8  700 500 375 280 - - LC1E500*
FRAME 9  1000 630 500 375 - - LC1E630*

Spare Coil For Contractors

Contactor Reference
3 Pole Contactors  
LC1E06…E25 LAEX12**
LC1E32/E38 LAEX2**
LC1E40/E65 LAEX3**
LC1E80/E95 LAEX4**
LC1E120/E160 LAEX5*
LC1E200/E250 LAEX6**
LC1E300 LAEX7**

Coil Voltage Code

VOLTAGE (V AC) 24 110 220 415
LC1E06..LC1E95 B7 F7 M7 N5
LC1E120..LC1E300 B5 F5 M5 N5
LC1E400..LC1E630 B7 F7 M7 N7
LC1E06.. LC1E40B -   M5WB N5WB

Power Contractors ETVS ( 4 Pole AC Control )

Frame AC-1 Rating Power
Poles
Reference Power Poles Reference
FRAME-1     20 4NO LC1E06004*IN Pole2NO + 2NCs Refere LC1E06008*IN
25 4NO LC1E09004*IN 2NO + 2NC LC1E09008*IN
32 4NO LC1E12004*IN 2NO + 2NC LC1E12008*IN
40 4NO LC1E18004*IN 2NO + 2NC LC1E18008*IN
FRAME-2    50 4NO LC1E25004*IN 2NO + 2NC LC1E25008*IN
55 4NO LC1E32004*IN 2NO + 2NC LC1E32008*IN
60 4NO LC1E38004*IN 2NO + 2NC LC1E38008*IN
FRAME-3   75 4NO LC1E40004*IN 2NO + 2NC LC1E40008*IN
85 4NO LC1E65004*IN 2NO + 2NC LC1E65008*IN
Frame AC-1 Rating Power
Poles
Reference Power Poles Reference
FRAME-4 110 4NO LC1E80004*IN 2NO + 2NC LC1E80008*IN
  125 4NO LC1E95004*    

Control Relays-CAE

AUXILIARY        AC CONTACTS NC Reference
4 0 CAE40*
3 1 CAE31*
2 2 CAE22*

Spare Coil For Contractors

Ccontactor Reference
4 Pole Contactors  
LC1E0600*…. LC1E1800* LAEX1T**
LC1E2500*…. LC1E3800* LAEX2T**
LC1E4000*…..LC1E9500* LAEX4T**
Control Contactors  
CAE* LAEX12**

Coil Voltage Code

* Voltage (V AC) 24 110 220 220
LC1E0600*…9500* 50/60 Hz B7 F7 - -
LC1E0600*…9500* 50 Hz/ Wide Band - - M5WB N5WB
Control relay CAE 50 Hz B5 F5 M5 N5

Accessories- For ETVS Contractors

Description For Use with Mounting Contacts Reference
Auxiliary contact block LC1E06..E630 & LC1E0600..E9500 FRONT 1NO+1NC LAEN11
2NO LAEN20
2NC LAEN02
2NO+2NC LAEN22
4NO LAEN40
Star delta timer   LAETSD

Description For Use with Coil Voltage Reference
Surge suppressor*   LC1E06...E95 24..48V AC LAERCE
LC1E06...E95 110..240V AC LAERCU

Description For Use with Reference
Mechanical Interlock     LC1E06..E65 & LC1E0600*..E3800* LAEM1
LC1E80/E95 & LC1E4000*…LC1E9500* LAEM4
LC1E120..E160 LAEM5
LC1E200/E250 LAEM6

3 Pole Accessories Compatibility

Contactor Built in contacts LAEN.. LAERC LAEM
LC1E06 1NO or 1NC 1 1         1
LC1E09
LC1E12
LC1E18
LC1E25 1
LC1E32
LC1E38
LC1E40B
LC1E40
LC1E50
LC1E65
LC1E80 1NO or 1NC
LC1E95
LC1E120
LC1E160
LC1E200 1
LC1E250
LC1E300
LC1E400
LC1E500
LC1E630

4 Pole Accessories Compatibility

Contactor LAEN..       LAEM LAERC.
LC1E06      1      1      1
LC1E09
LC1E12
LC1E18
LC1E25
LC1E32
LC1E38
LC1E40
LC1E50
LC1E65
LC1E80
LC1E95

Control Relay Accessories Compatibility

Control Relay LAEN* LAERC
  CAE 1 of   1   
LAEN11 or
LAEN20 or
LAEN02 or
LAEN22

Thermal Overloade Relay-ETVS

Thermal Protection Adjustment Range For Use with Contactor Reference
LRE    
0.25...0.4 E06...E38 LRE03
0.4...0.63 E06...E38 LRE04
0.63...1 E06...E38 LRE05
1...1.6 E06...E38 LRE06
1.6...2.5 E06...E38 LRE07
2.5...4 E06...E38 LRE08
4...6 E06...E38 LRE10
5.5...8 E09...E38 LRE12
7...10 E09...E38 LRE14
9...13 E12...E38 LRE16
12...18 E18...E38 LRE21
16...24 E25...E38 LRE22
23...32 E25...E38 LRE32
30...38 E38 LRE35
17...25 E40...E95 LRE322
23...32 E40...E95 LRE353
30...40 E40...E95 LRE355
37...50 E50...E95 LRE357
48...65 E65...E95 LRE359

Thermal Protection Adjustment Range For Use with Contactor Reference
LRE    
55...70 E80...E95 LRE361
63...80 E80...E95 LRE363
80...104 E95 LRE365
51...81 E120...E300 LRE480
62...99 E120...E300 LRE481
84...135 E120...E300 LRE482
124...198 E160...E300 LRE483
146...234 E200...E300 LRE484
174...279 E250...E300 LRE485
208...333 E300 LRE486
258…414 E300…E400 LRE486

Accessories For Relay

Accessory For Relay Reference
Separate Mounting Block LRE01…LRE35 LAEB1
  LRE322…LRE365 LAEB3

Circuit breaker for motor protection-GZ1E- Pushbutton control motor protection circuit breaker - ETVS

Breaking Capacity
at 415 V 50 Hz
Motor Power AC3**          kW         hP Thermal Protection
Adjustment Range
Reference
GZ1-E Thermal Magnetic - With Pushbutton Control        
100 kA - - 0.1 - 0.16 GZ1E01
0.06 - 0.16 - 0.25 GZ1E02
0.09 - 0.25 - 0.40 GZ1E03
0.18 - 0.40 - 0.63 GZ1E04
0.37 0.5 0.63 – 1.0 GZ1E05
0.55 0.75 1.0 – 1.6 GZ1E06
0.75 1 1.6 – 2.5 GZ1E07
1.1 2 2.5 – 4 GZ1E08
2.2 3 4 – 6.3 GZ1E10
3 5.5 6 – 10 GZ1E14
10 kA* 5.5 7.5 9 – 14 GZ1E16
7.5 10 13 – 18 GZ1E20
9 12.5 17 – 23 GZ1E21
11 15 20 – 25 GZ1E22
15 20 24 – 32  

Breaking Capacity
at 415 V 50 Hz
Motor Power           AC3**          kW hP Magnetic Protection
Range (A)
Reference
GZ1-LE Magnetic- With Pushbutton Control        
100 kA 0.09 - 0.4 GZ1LE03
0.18 - 0.63 GZ1LE04
0.37 0.5 1 GZ1LE05
0.55 0.75 1.6 GZ1LE06
0.75 1 2.5 GZ1LE07
1.1 2 4 GZ1LE08
2.2 3 6.3 GZ1LE10
3 5.5 10 GZ1LE14
10 kA* 5.5 7.5 14 GZ1LE16
7.5 10 18 GZ1LE20
11 15 25 GZ1LE22
15 20 32 GZ1LE32

Accessories- ETVS Circuit Breaker For Motor Protection

Description Mounting Contacts Reference
Auxillary Contact
Block
LH side Mounted 1NO+1NC GZ1AN11
    2NO GZ1AN20
Request A Quote